SKRIPSI DIGITAL

Analisis Pengaruh Variasi Laju Aliran Massa Fluida Dingin Terhadap Efektivitas Penukar Kalor Selongsong dan Tabung tipe Aliran Berlawanan Menggunakan Ansys Fluent = Analysis of Cold Fluid Mass Flow Rate Variations Effect on Counter-Flow Shell and Tube Heat Exchanger Effectiveness Using ANSYS Fluent

Irvin Satrio Herlambang - Nama Orang; Nur Fatowil Aulia - Nama Orang; Anis Roihatin - Nama Orang;

A shell and tube heat exchanger is one of the most widely used heat transfer devices in energy systems and industrial applications. Its performance is influenced by operating conditions,particularly the fluid mass flow rate. This study aims to analyze the effect of cold-fluid mass flowrate variations on the heat transfer rate,Log Mean Temperature Difference (LMTD), effectiveness,and flow characteristics of a counterflow shell-and-tube heat exchanger. Cold-water mass fow ratesof 0.1,0.2, 0.3, 0.4, and 0.5 kg/s were applied to evaluate the gradual changes in heat exchangerperformance. Therminol 66 and Marlotherm SH were alternately used as comparative hot fluids dueto their different thermophysical properties, allowing their thermal responses to be evaluated underidentical geometry and operating conditions. The study was conducted numerically using the Computational Fluid Dynamics (CFD) method with ANSYS Fluent 2026 R1.Water flowed throughthe tube side, while the hot fluid flowed through the shell side at a constant mass flow rate of 0.1kg/s. The inlet temperatures of the cold and hot fluids were maintained at 300 K and 373.15 K,respectively. The CFD model employed a selected mesh of 255,267 cells based on a grid independence test and showed good agreement with the reference data. The results indicate that increasing the cold-fluid mass flow rate increased the actual heat transfer rate and heat exchangereffectiveness.For Therminol 66, the actual heat transfer rate increased from 2.018 kW to 2.247kW,while the effectiveness increased from 15.16% to 16.90%. For Marlotherm SH, the actual heat transfer rate increased from 2.054 kW to 2.294 kW, while the effectiveness increased from 15.37% to 17.19%. The LMTD increased up to a cold-fluid mass flow rate of 0.4 kg/s,reaching maximumvalues of 66.404 K for Therminol 66 and 66.133 K for Marlotherm SH, before slightly decreasingat 0.5 kg/s. CFD visualization showed the formation of crossflow and recirculation zones on theshell side,while increasing the cold-fluid mass flow rate on the tube side increased the flow velocityand indicated a tendency toward flow maldistribution.Overall,increasing the cold-fluid mass flowrate within the investigated range improved the thermal performance of the heat exchanger,withthe highest effectiveness of 17.19% obtained using Marlotherm SH at a cold-fluid mass flow rate of 0.5kg/s.


Fulltext
  • Harap masuk untuk melihat lampiran
Informasi Detail
Judul Seri
-
No. Panggil
PE 026 2026
Penerbit
Semarang : Politeknik Negeri Semarang., 2026
Deskripsi Fisik
xviii, 122 hal.: illus.; 30 cm
Bahasa
Indonesia
ISBN/ISSN
-
Klasifikasi
NONE
Tipe Isi
text
Tipe Media
computer
Tipe Pembawa
online resource
Edisi
-
Subjek
EFEKTIVITAS
LMTD
computational fluid dynamics (cfd)
shell and tube heat exchanger
laju aliran massa
counterflow
Info Detail Spesifik
-
Pernyataan Tanggungjawab
Irvin Satrio Herlambang
Versi lain/terkait

Tidak tersedia versi lain

Komentar

Anda harus masuk sebelum memberikan komentar

  • Panduan
  • Area Anggota

Tentang Kami

Si-Repo adalah platform digital yang dikelola oleh UPA Perpustakaan Politeknik Negeri Semarang, menyimpan karya ilmiah seperti Tugas Akhir, Skripsi, dan Tesis dari sivitas akademika Polines, untuk mendukung kebutuhan akademik, penelitian, dan pengembangan.

Jam Buka Perpustakaan

Senin - Kamis:
07.30 - 16.00 WIB

Jum'at:
07.30 - 16.30 WIB


NPP. 3374102C0000002
0895340731030
Follow Us
Subscribe

© 2026 — Perpustakaan Politeknik Negeri Semarang

Ditenagai oleh SLiMS
Pilih subjek yang menarik bagi Anda
  • Karya Umum
  • Filsafat
  • Agama
  • Ilmu-ilmu Sosial
  • Bahasa
  • Ilmu-ilmu Murni
  • Ilmu-ilmu Terapan
  • Kesenian, Hiburan, dan Olahraga
  • Kesusastraan
  • Geografi dan Sejarah
Icons made by Freepik from www.flaticon.com
Pencarian Spesifik
Kemana ingin Anda bagikan?