Analisa Proteksi Over Current Relay ( OCR ) Dan Ground Fault Relay ( GFR ) Pada Transformator Daya 1 Gardu Induk Wonogiri = Analisa Proteksi Over Current Relay ( OCR ) Dan Ground Fault Relay ( GFR ) Pada Transformator Daya 1 Gardu Induk Wonogiri

Ja'Far Shodiq - Nama Orang; JA'FAR SHODIQ [IL] - Nama Orang; SYAHID - Nama Orang; Mochammad Muqorrobin - Nama Orang;

ABSTRAK

Penelitian ini menganalisis jenis dan karakteristik gangguan hubung singkat pada Transformator Daya #1 GI Wonogiri, khususnya pada penyulang WNI01 dan sisi incoming. Gangguan yang terjadi berupa arus lebih dan hubung singkat fasa ke tanah dengan besaran arus mencapai 4.255,67 A pada penyulang WNI01 dan hingga 104.068,78 A pada sisi incoming. Evaluasi kinerja proteksi menunjukkan adanya perbedaan signifikan antara setting relai eksisting dan terbaru.
Pada penyulang WNI01, GFR eksisting bekerja terlalu cepat (1,38687 s), sedangkan setting terbaru lebih selektif (1,5072 s). OCR eksisting sangat cepat (0,216 s) sehingga berpotensi salah trip, sementara setting terbaru (1,08078 s) lebih sesuai standar koordinasi. Pada sisi incoming, GFR terbaru mempercepat respon sebesar 6,70% dibanding eksisting, dan OCR terbaru menunjukkan peningkatan kecepatan sebesar 0,99%
Hasil analisis menegaskan bahwa setting terbaru lebih sesuai dengan standar inverse time, meningkatkan selektivitas koordinasi, serta memperbaiki keandalan sistem dalam membedakan gangguan sementara dan permanen. Rekomendasi penelitian ini adalah mempertahankan setting terbaru OCR dan GFR, melakukan simulasi kurva koordinasi waktu–arus (TCC), serta melaksanakan evaluasi berkala terhadap data gangguan nyata di lapangan agar sistem proteksi tetap adaptif dan kontinuitas penyaluran energi listrik terjamin.
Kata kunci : Gangguan hubung singkat, Transformator daya, Overcurrent Relay (OCR), Ground Fault Relay (GFR), Koordinasi proteksi, Keandalan sistem tenaga listri, dan Kurva waktu–arus (TCC)

Abstract : This study analyzes the types and characteristics of short-circuit faults on Power Transformer #1 at Wonogiri Substation (GI Wonogiri), particularly on feeder WNI01 and the incoming side. The faults observed include overcurrent and single-phase-to-ground short circuits, with current magnitudes reaching 4,255.67 A on feeder WNI01 and up to 104,068.78 A on the incoming side. The evaluation of protection performance reveals significant differences between the existing and updated relay settings.
On feeder WNI01, the existing GFR operated too quickly (1.38687 s), while the updated setting was more selective (1.5072 s). The existing OCR operated very fast (0.216 s), risking false tripping, whereas the updated setting (1.08078 s) was more in line with coordination standards. On the incoming side, the updated GFR accelerated response by 6.70% compared to the existing setting, and the updated OCR showed a slight improvement of 0.99%.
The results confirm that the updated settings are more consistent with inverse time standards, enhance selectivity in coordination, and improve system reliability in distinguishing between temporary and permanent faults. Recommendations include maintaining the updated OCR and GFR settings, conducting time–current coordination (TCC) curve simulations, and performing periodic evaluations of real fault data to ensure adaptive protection settings and guarantee continuity of power supply.
Keywords : Short-circuit fault, Power transformer, Overcurrent Relay (OCR), Ground Fault Relay (GFR), Protection coordination, Power system reliability, Time–current curve (TCC)


Fulltext
  • IL002-2026
Informasi Detail
Judul Seri
-
No. Panggil
IL 002 2026
Penerbit
Semarang : Politeknik Negeri Semarang., 2026
Deskripsi Fisik
xi, 59 hal.: illus., 30 cm.
Bahasa
Indonesia
ISBN/ISSN
-
Klasifikasi
NONE
Tipe Isi
text
Tipe Media
computer
Tipe Pembawa
online resource
Edisi
-
Subjek
transformator daya
gangguan hubungan singkat
gangguan hubung singkat
Overcurrent Relay (ocr)
ground fault relay (gfr)
koordinasi proteksi
kendala sistem tenaga listrik
kurva waktu-arus (tcc)
Info Detail Spesifik
-
Pernyataan Tanggungjawab
Ja'Far Shodiq
Versi lain/terkait

Tidak tersedia versi lain

Komentar

Anda harus masuk sebelum memberikan komentar

  • Panduan
  • Area Anggota

Tentang Kami

Si-Repo adalah platform digital yang dikelola oleh UPA Perpustakaan Politeknik Negeri Semarang, menyimpan karya ilmiah seperti Tugas Akhir, Skripsi, dan Tesis dari sivitas akademika Polines, untuk mendukung kebutuhan akademik, penelitian, dan pengembangan.

Jam Buka Perpustakaan

Senin - Kamis:
07.30 - 16.00 WIB

Jum'at:
07.30 - 16.30 WIB


NPP. 3374102C0000002
0895340731030
Follow Us
Subscribe

© 2026 — Perpustakaan Politeknik Negeri Semarang

Ditenagai oleh SLiMS
Pilih subjek yang menarik bagi Anda
  • Karya Umum
  • Filsafat
  • Agama
  • Ilmu-ilmu Sosial
  • Bahasa
  • Ilmu-ilmu Murni
  • Ilmu-ilmu Terapan
  • Kesenian, Hiburan, dan Olahraga
  • Kesusastraan
  • Geografi dan Sejarah
Icons made by Freepik from www.flaticon.com
Pencarian Spesifik
Kemana ingin Anda bagikan?